Tyndale's NFPA 70E Made Easy:

130.5 (H) – Equipment Labels

Section 130.5 (H) contains criteria that must be included on labeling for nonresidential electrical equipment that’s likely to be examined, adjusted, serviced, or maintained while energized—allowing workers to understand at-a-glance the risk, arc flash boundary, and necessary PPE.

After identifying the hazard potential through the tables method or an incident energy study, that information must be conveyed to workers who may interact with the equipment—by attaching  a physical label to the equipment. 

To protect workers, NFPA 70E includes specific requirements for labeling nonresidential equipment that’s likely to be examined, adjusted, serviced, or maintained while energized.

What does NFPA 70E say about labels?

In 130.5(H), NFPA 70E stipulates that electrical equipment labels shall contain the following:

  1. Nominal system voltage
  2. Arc flash boundary
  3. At least one of the following:
    • Available incident energy and the corresponding working distance, or the arc flash PPE category in Table 130.7(C)(15)(a) [for AC systems] or 130.7(C)(15)(b) [for DC systems] for the equipment, but not both
    • Minimum arc rating of clothing [Either a calorie level or PPE Category (#1-4)]
    • Site-specific level of PPE

This information helps workers 1) select the appropriate shock PPE, 2) identify the distance beyond which unqualified personnel must not pass, and inform technicians when PPE is required due to exposed live parts, and 3) wear appropriate arc flash PPE.

Two exceptions are noted:

  • Labels compliant with previous editions are still acceptable.

However, Jason emphasizes keeping your labels up to date—updating them every five (5) years to maintain alignment with the IEEE 1584 calculations that are revised every five (5) years.

  • In supervised industrial sites where all maintenance technicians are qualified, labeling each piece of gear is not required as long as the information is readily accessible to technicians (e.g., in a 3-ring binder).

However, Jason recommends utilizing physical labels on the equipment to make it easier for workers to access the safety information they need to stay safe.

The standard additionally states:

  • The method of calculating the data to support the information on the label shall be documented and reviewed every five years (or less)—and labels must be updated accordingly.
  • Labels must be made from durable materials.

What do compliant labels look like?

In the video above, Jason shares examples of acceptable labels from NFPA 70E Exhibit 160.5.

What types of electrical equipment require labels?

Switchboards, panelboards, industrial control panels, meter socket enclosures, motor control centers, etc.

Who is responsible for the labels?

The equipment owner is responsible for the documenting, installing, and maintaining the labels.

What about the NEC (NFPA 70)?

Historically, the NEC required general labels alerting unqualified persons to the presence of a hazard, but unlike NFPA 70E, detail beyond that was simply recommended and enforced indirectly.

However, beginning with the 2026 edition, the NEC now explicitly requires labels to include four key pieces of information:

  • The nominal system voltage
  • The arc flash boundary
  • The available incident energy or minimum required level of personal protective equipment
  • The date the assessment was completed.

These new label requirements largely align with NFPA 70E, except “working distance” is not included and the “equipment assessment date” is added to the NEC version.

  • The video above includes samples of NEC-compliant labels—and a side-by-side comparison of new NEC labels and NFPA 70E labels.
  • Concerned about juggling both types of labels? Jason recommends adding “date of assessment” to your 70E-compliant labels—rendering them compliant with both standards.

Clear labeling is not only required but it’s essential for keeping technicians safe—eliminating any guesswork or legwork with identifying the hazard and appropriate PPE.

Tyndale’s "NFPA 70E Made Easy" video series – hosted by Jason Brozen, Tyndale’s Lead Corporate Safety and Technical Trainer, a 28-year Master Electrician and an NFPA Certified Electrical Safety Compliance Professional (CESCP) – makes electrical safety accessible and understandable for all. The series delves into the intricacies of NFPA 70E, a vital tool since 1979 for establishing practical and safe workplaces. Recognizing its significance, we’ve created an entire educational resource hub dedicated to this essential standard, offering comprehensive insights and guidance.