This section of NFPA 70E covers the electric shock risk assessment – one of the most important steps to keeping you safe.

This section of NFPA 70E contains one of the most important steps to keeping you safe: the electric shock risk assessment (ESRA).

This important evaluation determines if any electrical part will be energized during any part of the task, and must be completed for every task with potential risk involved.

There are many questions that need to be answered before you proceed, starting with whether the work is justified. You’ll also have to consider the hazards present, risks to other employees, qualifications of personnel, safety plans for the task, and more.

In the video training sessions above, Jason covers sub-parts A through G of 130.4:

A) Reasons for performing the Electric Shock Risk Assessment:

  1. To identify shock hazards
  2. Estimate likelihood and severity of injury
  3. Determine if any additional protective steps are needed

B) Considerations for estimating the likelihood and severity of injury:

  1. The design of the electrical equipment
  2. Its operating condition and how it’s been maintained

C) Additional protective measures:

  1. a. If these are required, they are to be selected and implemented based on the hierarchy of risk controls identified in 110.3(H)(3).
  2. b. When additional protective measures include the use of personal protection equipment (PPE), you’ll need to determine:
    1. i. The voltage to which personnel will be exposed
    2. ii. The boundary requirements (more on this to come in our next session!)
    3. iii. PPE and other protective equipment required by NFPA 70E to protect against electric shock hazard

D) This entire process shall be documented. Remember: OSHA isn’t interested in what you say you did, only what you have documented.

E) Electric shock protection boundaries: this is applicable where personnel are approaching exposed energized electrical conductors or circuit parts. Pay special attention, as this is one of the most misunderstood topics in NFPA 70E.

  • The section provides two tables that are used to identify approach distances.
    • Table 130.4(E)(a) is for alternating current (AC) approach boundaries.
    • Table 130.4(E)(b) is for direct current (DC) approach boundaries.
  • There are two approach distances, which help workers understand where to initiate safe work practices – including tools, PPE, energized work permits, etc.:
    • The limited approach boundary is farther from the hazard and applies to unqualified personnel.
    • The restricted approach boundary is closer to the hazard and applies to qualified personnel.

F) This section addresses the limited approach boundary.

  • Unless permitted by 130.4(F)(3), no unqualified person shall be permitted to approach closer than the limited approach boundary.
  • If there are unqualified persons working at or close to the limited approach boundary, 130.8(O) should be used to alert and warn them to stay outside of the boundary.
    • This usually entails creating a physical barrier to mark the boundary.
    • We’ll take a closer look at 130.8(O) in an upcoming video training session.
  • In the rare situation in which an unqualified person may need to temporarily enter or pass through the work area, the qualified person must advise the unqualified person of the hazard and continuously escort them during their time inside the limited approach boundary.
  • Under no circumstances are unqualified personnel allowed to cross the restricted approach boundary.

G) This section addresses the restricted approach boundary.

  • The standard indicates that no qualified person shall approach or take any conductive object closer to exposed energized electrical conductors or circuit parts than the restricted approach boundary set forth in table 130.4(E)(a) or 130.4(E)(b) unless one of the following conditions applies:
    • The qualified person is insulated or guarded from energized electrical conductors or circuit parts operating at 50 volts or more.
    • The energized electrical conductors or circuit parts are insulated from the qualified person and from any other conductive object at a different potential.
  • Your company will make this determination, and it must be documented, trained, and audited to ensure compliance.
  • Remember:
    • Only qualified people may enter that restricted approach boundary.
    • Any physical barricades will always be at least at the limited approach distance – farther from the hazard than the restricted approach boundary.
    • The energized electrical work permit is required in some situations when you enter the restricted approach boundary.

To continue learning about NFPA 70E, use the buttons below to view the next session in our series.   

Tyndale’s "NFPA 70E Made Easy" video series – hosted by Jason Brozen, Tyndale’s Lead Corporate Safety and Technical Trainer, a 28-year Master Electrician and an NFPA Certified Electrical Safety Compliance Professional (CESCP) – makes electrical safety accessible and understandable for all. The series delves into the intricacies of NFPA 70E, a vital tool since 1979 for establishing practical and safe workplaces. Recognizing its significance, we’ve created an entire educational resource hub dedicated to this essential standard, offering comprehensive insights and guidance.