Tyndale's NFPA 70E Made Easy:

130.2(A)(2) – Additional Person Requirement for Energized Work

NFPA 70E (2027), Section 130.2(A)(2) contains a new requirement for an additional person present during justified energized electrical work.

The 2027 edition of NFPA 70E introduces an entirely new Section 130.2, Work Involving Electrical Hazards. This new section includes 130.2(A)(2), which requires an additional person to be present for the performance of justified energized electrical work requiring an energized work permit. If you or your employees perform justified energized electrical work, this update may directly impact staffing, training, and overall compliance procedures.

What is the NFPA 130.2(A)(2): Additional Person Requirement?

The 2027 edition of NFPA 70E introduces an entirely new Section 130.2, Work Involving Electrical Hazards. This new section includes 130.2(A)(2), which requires an additional person to be present for the performance of justified energized electrical work requiring an energized work permit.

If you or your employees perform justified energized electrical work, this update may directly impact staffing, training, and overall compliance procedures.

What is the NFPA 130.2(A)(2): Additional Person Requirement?

Article 130 in NFPA 70E covers requirements for workers potentially exposed to electrical hazards while performing justified electrical work. This new section—130.2(A)(2)—requires an additional person to be present whenever someone is performing justified energized electrical work under certain conditions. The intent is for the additional person to be readily available to provide aid, should an emergency or injury occur.

When is an Additional Person Required Under NFPA 70E?

The conditions that require an additional person are:

  1. Energized work is justified (permitted when the employer can demonstrate that the task is infeasible in a de-energized state or that de-energizing introduces additional hazards or risk)
  2. An is required in accordance with 130.3
  3. Electric shock or arc flash PPE is required

Who Can Serve as an Additional Person?

An additional person must meet the emergency response training requirements outlined in NFPA 70E 110.4(C)(1) and be competent in the following:

  • Emergency response
  • Contact-release techniques
  • Electrical hazard awareness
  • Approach boundary education

It’s important to note that the additional person must remain outside the limited approach or arc flash boundary—whichever is greater—while energized electrical work is being performed. This distance is crucial to preventing multiple injuries. The additional person must be able to provide assistance in the event of an arc flash or other incident.

Does All Electrical Work Require an Additional Person?

There are certain exceptions for when the additional person requirement comes into effect. If the electrical tasks involve the following, an additional person may not be required:

  • Testing
  • Troubleshooting
  • Voltage measuring (without tools)

Also, the additional person rule does not apply if an energized electrical work permit (EEWP) or PPE are not required.

How the Additional Person Requirement Impacts Employers

It’s important for employers to understand the new requirement and plan accordingly, especially for small businesses with minimal staff.

Single-electrician jobs are a thing of the past for energized work environments. Adhere to  compliance requirements for the 2027 edition of NFPA 70E by:

  1. Updating processes for energized work environments
  2. Clearly defining responsibilities for workers performing energized work and the additional person (observer)
  3. Documenting any new training requirements

Frequently Asked Questions About NFPA 70E 130.2(A)(2)

1What is the NFPA 70E (2027) Additional Person Requirement?
NFPA 70E (2027), section 130.2(A)(2) states that an additional person must be present for the performance of justified energized electrical work that requires an energized electrical work permit (EEWP) or personal protective equipment (PPE).
2When does NFPA 70E require an additional person?
An additional person is required any time energized electrical work requires an energized electrical work permit (EEWP) or personal protective equipment (PPE).
3Can a safety professional serve as an additional person?
The additional person can be a licensed electrician or any safety professional, so long as they meet the emergency response safety requirements as outlined in NFPA 70E 110.4(C)(1).
4Does OSHA require two people for energized electrical work?
Yes, OSHA generally requires two people for energized electrical work when voltage surpasses 600V but also defaults to NFPA 70E for energized work requirements. Stay tuned for future updates and episodes as additional information is released for NFPA 70E (2027).

Stay tuned for future updates and episodes as additional information is released for NFPA 70E (2027).

Tyndale’s "NFPA 70E Made Easy" video series – hosted by Jason Brozen, Tyndale’s Lead Corporate Safety and Technical Trainer, a 28-year Master Electrician and an NFPA Certified Electrical Safety Compliance Professional (CESCP) – makes electrical safety accessible and understandable for all. The series delves into the intricacies of NFPA 70E, a vital tool since 1979 for establishing practical and safe workplaces. Recognizing its significance, we’ve created an entire educational resource hub dedicated to this essential standard, offering comprehensive insights and guidance.


Important Disclaimer

The content provided is for informational purposes only. We strive for accuracy, however, make no representations about completeness, reliability, or suitability and are not liable for loss or damage arising from use. By accessing this information, you agree to these terms.