Tyndale's NFPA 70E Made Easy:

130.1 – Work Involving Electrical Hazards, Scope

In previous education sessions as part of this series, we covered how NFPA 70E Article 120 emphasizes the importance of establishing an electrically safe work condition (ESWC) before employees work on or near electrical conductors or circuit parts that otherwise are, or can become, energized.

In the video, Jason points out that establishing an ESWC is mandatory, except in very rare cases. Article 130 focuses on the general requirements for electrical safety-related work practices when an ESWC cannot be established, explaining the regulations for those rare cases when working energized cannot be avoided. We’ll first recap what working energized means and then get into how to stay safe if an ESWC cannot be established and you must work energized.

What does ‘working energized’ mean?

“Working energized” refers to intentionally encountering energized electrical conductors or circuit parts with any part of your body, tools, probes, or test equipment, regardless of the personal protective equipment (PPE) you’re wearing. Examples of working energized include:

  • Diagnostic testing, such as taking readings or measurements of electrical equipment, conductors, or circuit parts with approved test equipment that does not require making any physical change to the electrical equipment, conductors, or circuit part(s).
  • Repairing or physically altering electrical equipment, conductors, or circuit parts, such as making or tightening connections, and removing or replacing components.

In previous content we’ve covered the myth of ‘de-energized work’, how to establish an ESWC where electrical conductors or circuit parts are properly de-energized, and the proper PPE to wear when doing so. In an upcoming episode on Section 130.2 of Article 130, we’ll cover what it means to work energized in more detail.

What happens when an ESWC cannot be established?

With over 70 pages of information included in Article 130 of the Handbook, the scope of the Article focuses on a few key points. Section 130.1- Scope, specifies that when energized electrical conductors and circuit parts operating at voltages of 50 volts or greater are not put into an electrically safe work condition, and work is performed as permitted in accordance with 110.2 (B), the following requirements shall apply:

  1. Only qualified persons shall be permitted to work on electrical conductors or circuit parts that have not been put into an electrically safe work condition. Employees must be trained to understand the hazards associated with electrical work and the necessary safety procedures.
  2. An energized electrical work permit shall be completed as required by 130.2.
  3. Employers must perform a risk assessment to identify hazards, assess risks, and implement control measures, including completing an electric shock risk assessment as required by 130.4.
  4. An arc flash risk assessment shall be performed as required by 130.5.

It's important to emphasize that you must follow the requirements outlined in Article 130 even if you have conducted a professional incident energy analysis or used the tables methods referenced in 130.7 to determine arc flash protection level requirements. Working with live electricity is extremely dangerous and should be avoided whenever possible. Unfortunately, many industries have become complacent about this issue, often pressuring employees to work on energized equipment. Since this practice poses significant risks, following the requirements outlined in Article 130 can mean the difference between life and death.

Tyndale’s "NFPA 70E Made Easy" video series – hosted by Jason Brozen, Tyndale’s Lead Corporate Safety and Technical Trainer, a 28-year Master Electrician and an NFPA Certified Electrical Safety Compliance Professional (CESCP) – makes electrical safety accessible and understandable for all. The series delves into the intricacies of NFPA 70E, a vital tool since 1979 for establishing practical and safe workplaces. Recognizing its significance, we’ve created an entire educational resource hub dedicated to this essential standard, offering comprehensive insights and guidance.


Important Disclaimer

The content provided is for informational purposes only. We strive for accuracy, however, make no representations about completeness, reliability, or suitability and are not liable for loss or damage arising from use. By accessing this information, you agree to these terms.