Tyndale's NFPA 70E Made Easy:

110.2B: When an Electrically Safe Work Condition is Required

This section of NFPA 70E outlines conditions under which energized electrical conductors and circuit parts operating at or over 50 volts shall be put into an electrically safe work condition before an employee performs work.

When is an ESWC required?

NFPA 70E 110.2B specifies an electrically safe work condition (ESWC) is required to work on electrical conductors and circuit parts operating at or above 50 volts when an employee is:

  • Within the limited approach boundary AND
  • Interacts with equipment where conductors or circuit parts are not exposed but an increased likelihood of injury from exposure to an arc flash hazard exists

What does it mean to “interact” with equipment?

This can mean anything from resetting breakers, pushing buttons, restarting motors, turning disconnects on and off, and any number of other routine tasks.

Does this mean you need to de-energize, fill out risk assessments, wear PPE, etc. to complete these routine tasks? That depends. The standard includes some exceptions:

  • Exception 1:
    • A normal operating condition exists – meeting ALL of the following conditions:
      1. Equipment is properly installed (per manufacturer instructions, permitting, etc.).
      2. Equipment is properly maintained.
      3. Equipment is rated for available fault current.
      4. Equipment is used in accordance with manufacturer and listing/labeling instructions.
      5. Equipment doors are closed and secured.
      6. Equipment covers are in place and secured (all covers and screws installed, fastened in place, etc).
      7. There is no evidence of impending failure.
    • In his 20+ years of experience as an electrician, Jason does not routinely encounter issues with criteria #1, 3, 4, and 7 from the above list. However,
      • Most of the equipment Jason has seen in the field is not properly maintained, posing a problem for criteria #2.
        • Take note: OSHA and the industry are actively addressing this gap. Unless you have manufacturer’s instructions available, you must become familiar with NFPA 70B, Standard for Electrical Equipment Maintenance – which recently underwent a status change from a recommended practice to a proscriptive standard, making it a requirement that you maintain an Electrical Maintenance Program (EMP).
          • Accordingly, OSHA will soon ask not only for your Electrical Safety Program (ESP) but also your EMP if someone gets injured.
          • It is not enough to say you comply with NFPA 70B, rather your EMP must be properly documented.
      • Jason only sometimes sees equipment doors closed and secured (criteria #5).
      • He rarely sees all panel covers and screws installed (criteria #6).
      • If the equipment you are working on demonstrates any of these common pitfalls, you are not covered by exception #1 and you would need to achieve an ESWC before performing work.
  • Exception 2: This exception is self-explanatory in the standard.
  • Exception 3: Energized work is permitted when the employer can demonstrate the task is infeasible in a de-energized state due to equipment design or operational limitations – tasks including but not limited to diagnostic testing, troubleshooting, or startup.
    • Keep in mind: infeasible does not mean impractical.
  • Exception 4: Energized work is permitted where the employer can demonstrate that de-energizing introduces additional hazards or increased risk – life and death scenarios like turning off things like life support systems, toxic or flammable gas ventilation, or emergency alarms.
    • You must provide documentation, rationale, and receive authorization.
    • Energized work is rarely justified in the eyes of NFPA 70E and OSHA.
  • Exception 5: Under 50 volts de-energizing is not necessary as long as you’ve at least considered the capacity of that circuit in overcurrent protection to make sure no explosion hazard exists.

Concerned about missing something? Follow the helpful flow chart in exhibit 110.1 to ensure you don’t miss any steps.

To continue learning about NFPA 70E, view the next session in our series, 110.2C – establishing and verifying an ESWC.   

Tyndale’s "NFPA 70E Made Easy" video series – hosted by Jason Brozen, Tyndale’s Lead Corporate Safety and Technical Trainer, a 28-year Master Electrician and an NFPA Certified Electrical Safety Compliance Professional (CESCP) – makes electrical safety accessible and understandable for all. The series delves into the intricacies of NFPA 70E, a vital tool since 1979 for establishing practical and safe workplaces. Recognizing its significance, we’ve created an entire educational resource hub dedicated to this essential standard, offering comprehensive insights and guidance.