Tyndale's NFPA 70E Made Easy:

110.2 (A) – Electrically Safe Work Condition (ESWC) Policy

This section of the NFPA 70E Series outlines the Electrically Safe Work Condition (ESWC) Policy.

The Policy states:

An employer shall establish, document, and implement an electrically safe work condition policy that does both of the following:

  1. Requires hazard elimination to be the first priority in the implementation of the safety-related work practices.
  2. Complies with 110.2B.

This section can sometimes be confusing, so let’s clarify: the Policy says that you must de-energize, if at all possible. This is crucial, particularly because we often hear in the field, “We don’t work anything hot. We lock everything out.” However, this statement is misleading, as properly locking something out entails verifying the absence of voltage – an essential step in energized work.

To back up this critical information, OSHA calls out the ESWC Policy in CFR 1910.333(a)(1):

“Live parts must be de-energized before the employee works on or near them. Performing energized work requires the employer to demonstrate de-energizing introduces additional or increased hazards or that it is infeasible due to equipment design or operational limitations.”

So, how do you de-energize? You must eliminate any hazards connected to the piece of equipment you’re working on.

Eliminating Hazards

Elimination is at the top of the Hierarchy of Risk Controls, as shown in the video graphic. Elimination means physically removing a hazard. This is what the ESWC Policy is referencing. There can be numerous hazards related to the type of equipment you’re working on, including:

  • Electrical 480 VAC hazards
  • Water hazards
  • Chemical or coolant hazards
  • Steam hazards
  • Pneumatic hazards
  • Natural gas hazards
  • Hydraulic hazards
  • Mechanical hazards

Disabling Power Isn't Always an Option

As demonstrated earlier, equipment may pose hazards beyond just electricity, meaning that simply cutting power won't guarantee safety. Take, for instance, a hospital transfer switch requiring maintenance. You can't just shut down both power sources without risking the lives of ICU patients reliant on life support. This is just one example of an exception that is prone to widespread misunderstanding – and exploitation.

In future videos, we'll delve into these exceptions and provide guidance on understanding them accurately.

Bottom Line

Remember: According to the ESWC Policy, you must de-energize, if at all possible. That means physically removing any hazards by de-energizing them before beginning work.

To continue learning about NFPA 70E, tune in to the next session in our series, NFPA 70E 110.2B – When an Electrically Safe Work Condition is Required.

Tyndale’s "NFPA 70E Made Easy" video series – hosted by Jason Brozen, Tyndale’s Lead Corporate Safety and Technical Trainer, a 28-year Master Electrician and an NFPA Certified Electrical Safety Compliance Professional (CESCP) – makes electrical safety accessible and understandable for all. The series delves into the intricacies of NFPA 70E, a vital tool since 1979 for establishing practical and safe workplaces. Recognizing its significance, we’ve created an entire educational resource hub dedicated to this essential standard, offering comprehensive insights and guidance.