FR Clothing Safety Standards: NFPA 70E, ASTM F1506, OSHA & More


Arc Flash Standards

OSHA 1910.269

Electric power generation, transmission, and distribution.

On April 1, 2014, OSHA announced the final rule revising the 1910.269 standards for electric power generation, transmission and distribution. This revised rule implements significant changes to utilities’ requirements for protecting workers from electric arcs and using flame resistant clothing, among other areas. Tyndale has compiled Arc Flash FAQs to address key questions on the ruling and how it impacts your company and your workers. Effective August 31, 2015, ruling requires companies to complete a hazard assessment by and comply with the requirements of the ruling, including the provision of PPE to employees appropriate to the risks of their work environments. Go to our blog for access to the ruling in both .pdf and word versions.

Several key provisions of the ruling are outlined below:

  • The employer shall ensure that each employee exposed to hazards from electric arcs wears protective clothing and other protective equipment with an arc rating greater than or equal to the heat energy estimate whenever that estimate exceeds 2.0 cal/cm2. “This protective equipment shall cover the employee’s entire body,” except for certain exemptions for hands, feet and head protection. This requirement replaced the previous, and now inoperative standard “…each employee who is exposed to the hazards of flames or electric arcs does not wear clothing that, when exposed to flames or electric arcs, could increase the extent of the injury that would be sustained by the employee.”
  • Pants and head protection must be provided to workers, in addition to PPE that protects the torso.
  • FR clothing is now considered PPE. Previously, FR clothing was not explicitly considered PPE. In the ruling, OSHA makes clear that it is the employer’s responsibility to ensure proper care and maintenance of employees’ protective clothing. OSHA is equally clear the final rule does not require employers to launder protective clothing for employees, but no longer can employers simply tell their workers to “follow washing instructions,” and trust that they will do so. “If employers rely on home laundering of the clothing, they must train their employees in proper laundering procedures and techniques, and employers must inspect the clothing on a regular basis to ensure that it is not in need of repair or replacement (p. 187).” And, employers who choose to utilize an industrial laundry service or other vendor are not absolved from this responsibility to inspect PPE directly.
  • In addition to flame resistant apparel, there are requirements for head protection. Face shields with minimum arc rating of 8 cal/cm2 are required (dependent on type of exposure) and arc-rated hood or face shield with balaclava is required at higher exposures. Download the FAQs from TyndaleUSA.com for details. Hand and foot protection is also discussed in the ruling; details are available in our on specific requirements.

NESC

The National Electrical Safety Code

Published by IEEE, the National Electrical Safety Code (NESC®) is a standard – adopted on the state level by state OSHA organizations– that sets the ground rules for practical safeguarding of workers during the installation, operation, or maintenance of electric supply and communication lines and associated equipment. This standard covers systems and equipment operated by utilities, or similar systems and equipment of an industrial establishment or complex under the control of qualified persons.

Adoption of the NESC varies by state. In areas where the code has been adopted, it is enforceable as law.

The NESC is revised every five years, with the 2023 edition being the most recent.

The standard can be purchased and downloaded from the IEEE website at https://standards.ieee.org/products-programs/nesc/

NFPA 70E

Standard for Electrical Safety in the Workplace®

NFPA 70E addresses electrical safety requirements necessary to safeguard employees during activities such as the installation, removal, inspection, operation, maintenance, and demolition of electric conductors, electric equipment, signaling and communications conductors and equipment, and raceways. 90.2(A)

Regarding work practices and electrical system maintenance, the NFPA 70E provides key information that is not included in the scope of the NFPA 70, the National Electric Code (NEC). While the NEC is useful for those responsible for the proper installation of electrical equipment, the NFPA 70E is a voluntary standard purposely geared toward workers and employers to understand and implement safety precautions. While OSHA uses the General Duty Clause as the basis for citations, OSHA commonly cites information from NFPA 70E as supporting information to enforce compliance regarding electrical safety.

  • Exclusions: A few industries are excluded from NFPA 70E: electric utility transmission, distribution, and generation workers (who are covered by OSHA 1910.269), as well as the marine, railway rolling stock, and communications equipment as specified in Article 90.3(B). Although not included in the scope of the 70E, many of these industries protect workers with arc-rated (AR) clothing as a general practice. It is important to note that all other affiliated outbuildings, maintenance facilities and general areas are covered by the scope of the 70E.
  • Arc flash PPE categories: NFPA 70E categorizes PPE for most electrical procedures into four levels and assigns minimum arc ratings for each PPE category (CAT) based on the hazard(s) present. These specifications are detailed in Table 130.7(C)(15)(c) of the 70E.

 

Other practical recommendations made within NFPA 70E address commonly asked questions on the topics below:

 

  1. Layering: “Nonmelting, flammable fiber garments shall be permitted to be used as underlayers in conjunction with arc-rated garments in a layered system. If nonmelting, flammable fiber garments are used as underlayers, the system arc rating shall be sufficient to prevent breakopen of the innermost arc-rated layer at the expected arc exposure incident energy level to prevent ignition of flammable underlayers. Garments that are not arc rated shall not be permitted to be used to increase the arc rating of a garment or of a clothing system. Informational Note: A typical layering system might include cotton underwear, a cotton shirt and trouser, and an arc-rated coverall. Specific tasks might call for additional arc-rated layers to achieve the required protection level.” 130.7(C)(9)(a)
  2. Underlayers: “Meltable fibers such as acetate, nylon, polyester, polypropylene, and spandex shall not be permitted in fabric underlayers. Exception: An incidental amount of elastic used on nonmelting fabric underwear or socks shall be permitted. 130.7(C)(9)(c)
  3. Coverage: “Clothing shall cover potentially exposed areas as completely as possible.  Shirt and coverall sleeves shall be fastened at the wrists, shirts shall be tucked into pants, and shirts, coveralls, and jackets shall be closed at the neck.” 130.7(C)(9)(d)
  4. Fit: “Tight-fitting clothing shall be avoided. Loose-fitting clothing provides additional thermal insulation because of air spaces. Arc-rated apparel shall fit properly such that it does not interfere with the work task.” 130.7(C)(9)(e)

 

The most recent update to NFPA 70E is the 2027 edition. Changes of note related to flame resistant protective apparel include:

  1. Protector revisions: Throughout the entire standard, the term “leather protectors” has been replaced with “protectors,” and a clear definition of “protector” was added in Article 100. The new definition states that a protector is “a glove or mitten to be worn over rubber insulating gloves.” This change aims to eliminate ambiguity and make the standard more precise.
  2. Closed doors and PPE: The informational note in Section 130.5 makes it clear that, in most cases, closed doors are not sufficient to eliminate the need for PPE. This note highlights that doors may not be able to contain all the energy during an arc flash and might blow open, which solidifies the need for PPE while switching or operating equipment that is not in a “normal” operating condition.
  3. Emphasis on operating condition: The 2024 version of NFPA 70E places a significant emphasis on “Operating Condition.” For instance, Table 130.5(C) now uses the term “Operating Condition” in place of “Equipment Condition” to align with the requirements for normal operating condition outlined in Section 110.2(B). A piece of equipment is in “normal operating condition” when specific conditions are met, including proper installation, maintenance, rating for available fault current, usage in accordance with instructions, and other requirements.
  4. Hearing protection: Section 130.7(C)(5) has been adjusted regarding hearing protection. The word “working” was removed from the previous text, which read “whenever working within the arc flash boundary.” Now, anyone inside the arc flash boundary must wear hearing protection, regardless of whether they are actively working. This change recognizes that being within the boundary poses a risk to hearing, irrespective of one’s specific tasks.
  5. Arc flash PPE categories for DC systems: In Section 130.7(C)(15)(b), the table that outlines arc flash PPE categories for DC systems, such as storage batteries, DC switchboards, and other DC supply sources, has been updated. The value range requiring arc flash PPE has increased from 100 – 250 VDC to 150 – 600 VDC. This change is supported by recent test data for a maximum arc duration of 2 seconds and a minimum working distance of 18 inches.
  6. Informative Annex S:While not a part of the requirements, this newly added informational annex addresses maintenance conditions. Of particular interest is Section 8, which references NFPA 70B, Standard for Electrical Equipment Maintenance. NFPA 70B recently underwent a status change from a guide – a recommended practice indicating what you should do – to a standard – making it a requirement. This change increases the necessity for PPE since NFPA 70B contains further information on safeguarding practices.

 

  • Changes of note related to AR / FR in the previous editions of NFPA 70E include:

 

  • 2021 edition:

 

  • Non-FR heraldry (logos, patches, etc.) used on FR garments: Informational Note No. 2 was added to section 130.7 C 13d which points to ASTM 1506 for additional guidance regarding the addition of trim, name tags, logos, etc. to arc rated clothing. ASTM 1506-20A now specifies that non-FR heraldry should be limited to 40 square inches per garment, and no single piece of non-FR heraldry may exceed 16 square inches.
  • Arc rating of outer layers: Clarification was added, stating “The arc rating of outer layers worn over arc-rated clothing as protection from the elements or for other safety purposes, and that are not used as part of a layered system, shall not be required to be equal to or greater than the estimated incident energy exposure.” Since the arc rating of the clothing worn under the outerwear should sufficiently protect the wearer if it meets the required calorie rating, the outwear can now have a lower calorie rating. (NFPA 70E-2021, 130.7(C)9(b))
  • Maximum voltage for rubber insulating gloves: Table 130.7(C)(7)(a) was added, listing the different classes of gloves, their maximum AC and DC voltage ratings, and the minimum distance between gauntlet of the leather protector and cuff of the rubber glove.
  • Personal and other protective equipment: A note was added to section 130.7(C)(1) listing risk reduction methods to reduce the occurrence or severity of an incident when the estimated incident energy exposure is greater than available arc-rated PPE:
    • Use of a non-contact proximity tester before using a contact testing instrument
    • If equipment design allows, look for visible gaps between the equipment conductors and circuit parts and the electrical source. For example, if there is a switch, is it open?
    • Increase working distance. The exposure energy decreases the further a worker is from the hazard.
    • Choosing different equipment and configuration options to reduce the incident energy level.

 

  • PPE testing and standards: These standards have been moved to an informational note within this section and now include references to IEC standards (IEC 61482-1-1 & IEC 61482-2) in order to be more applicable to international practices.

 

  • 2018 edition:

 

  • All mandatory references to third party standards were removed: References to ASTM 1959 (arc rating of AR/FR textiles), ASTM 1506 (garment construction of AR/FR apparel) have been moved to informational notes and mandatory language was removed.
  • Addition of Table 130.5(C): This new table replaces Table 130.7(C)(15)(A)(a) from the 2015 edition and estimates of the likelihood of the occurrence of an arc flash Incident for AC and DC systems.
  • Addition of Table 130.5(G): This new table replaces Table H.3(b) from Annex H of the 2015 edition and identifies arc-rated clothing and other PPE when the incident energy analysis method is used.
  • Revision of footnote for Table 130.7(C)(7): This pertains to rubber insulating equipment – blankets, gloves, and sleeves. New equipment is not permitted to be placed into service unless it has been electrically tested within the previous 12 months and is required to be retested at the intervals shown in this table.
  • 130.7(C)(14)(b) Conformity Assessment: New guidelines were established to determine how a supplier should classify their products, allowing any of the following methods:
    • Self-declaration with a Supplier’s Declaration of Conformity, or
    • Self-declaration under a registered quality management system and product testing by an accredited laboratory and a Supplier’s Declaration of Conformity, or
    • Certification by an accredited independent third-party certification organization

 

  • 2015 edition:

 

  • Elimination of Category 0: This category allowed non-FR but non-melting fabrics such as flammable cotton; it was removed. Any situation with an arc flash hazard now requires arc-rated FR clothing.
  • HRC Category renamed PPE Category: This change is semantic only; the math and logic did not change, but the name was changed to better reflect the purpose. External labeling which used to say “HRC 2” is now designated as “CAT 2.”
  • Addition of a yes/no chart to determine if an arc flash hazard exists— Table 130.7(C)(15)(A)(a) identifies when arc flash PPE is required.
  • Conductive articles are not permitted to cross the “restricted approach boundary.”
  • Mining industry is now covered by 70E: The mining exemption in the scope was removed.

 

  • 2012 edition:

 

  • New terminology (Arc-Rated): Flame resistant (FR) was changed to “arc-rated (AR)” regarding personal protective equipment (PPE) throughout the standard.
  • Arc flash calculations in Annex D were updated to align with the 2012 version of the NESC.
  • Hazard/risk category tables were changed to include short-circuit current, fault clearing time, and potential arc flash boundary in each of the major equipment categories instead of in specific notes at the end of the table.
  • Head protection requirement:
    • Hazards less than 12 cal/cm2: An arc-rated hood or balaclava with an arc-rated faceshield must be used when the back of the head is exposed within the arc flash boundary when the hazard is between 1.2cal/cm2and 12 cal/cm2.
    • Hazards greater than 12 cal/cm2: An arc-rated hood alone must be used for hazards greater than 12 cal/cm2.

 

  • DC voltages: Historically, NFPA 70E has focused primarily on AC (alternating current) voltages. The 2012 NFPA 70E includes more information about calculating and protecting against DC (direct current) voltages. Table 130.4(E)(b) on p. 26 of NFPA 70E 2021 is used for calculating distances for direct-current voltage systems.
  • Arc flash boundary: A specific boundary for each task was added to a new column. This addition aligns with the deletion of the “four foot rule” in the 2009 Edition.
  • Building clarification: Section 90.2(A)(2) was revised to say, “Installations used by the electric utility, such as office buildings, warehouses, garages, machine shops, and recreational buildings that are not an integral part of a generating plant, substation, or control center.” This deletion clarifies that NFPA 70E applies to these areas, even if they are part of a generating plant, substation or control center.

 

  • The NFPA 70E standard and handbook are available in the following formats:

 

  • The printed softbound Standard for Electrical Safety in the Workplace® contains the full text of the standard and is available for purchase at nfpa.org/codes-and-standards/7/0/e/70e.
  • The printed hardbound Handbook for Electrical Safety in the Workplace is available for purchase at nfpa.org/product/nfpa-70e-handbook/p0070ehb. It contains the full text of the standard plus expert commentary, diagrams, and additional materials that, while not enforceable, aid in comprehending and applying the standard.
  • The digital edition, NFPA LiNK®, is available as a subscription using either of the above links. It provides online access to over 1,500 NFPA® codes and standards. NFPA LiNK® also includes expert commentary, diagrams, and additional materials that, while not enforceable, aid in comprehending and applying the standards.
  • A Free Access link to the standard’s text displayed in an online viewer is available at nfpa.org/codes-and-standards/7/0/e/70e.

Read our NFPA 70E FAQ.

ASTM F1506

Standard Performance Specification for Flame Resistant and Electric Arc Rated Protective Clothing Worn by Workers Exposed to Flames and Electric Arcs

This is the governing ASTM Standard for Flame Resistant Clothing. The standard has two basic requirements:

  • A sample of fabric must self-extinguish with less than 2 second after flame and less than 6″ char length according to ASTM Test Method D6413. This flammability test applies to an initial sample and after 25 wash cycles.
  • The fabric must be tested for Arc Thermal Performance according to ASTM Test Method F1959. The results of the Arc Thermal Performance testing must be reported to the end user as an Arc Rating on a garment label.
  • Different colors of the same fabric do not need to be tested separately.

A garment that meets ASTM F1506 complies with OSHA 1910.269, NESC, and NFPA 70E. ASTM F1506 is a pass/fail standard with requirements for reporting additional information not considered for the pass/fail criteria. All garments compliant to ASTM F1506 must be labeled with a tracking code, a statement that the garment meets the requirements of ASTM F1506, the manufacturer’s name, size information, care instructions, fiber content and the arc rating.

The standard can be purchased and downloaded from the ASTM website at http://www.astm.org/Standards/F1506.htm

ASTM F1959

Standard Test Method for Determining the Arc Rating of Materials for Clothing

ASTM F1959 is the test method used to calculate quantitative results (arc ratings) for FR fabrics. Arc ratings are a measure of thermal protection provided by the fabric in an arc flash.

  • The purpose of this test method is to determine how much heat a certain fabric (or system of fabrics) will block from an electric arc before the onset of second degree burns for the wearer.
  •  The amount of energy blocked by the fabric is reported as Arc Thermal Performance Value (commonly abbreviated as ATPV).  The value is reported as Energy Breakopen Threshold (Ebt) if the fabric breaks open before the onset of second degree burns is reached.
  • Heat Attenuation Factor (the percentage of total heat blocked by the fabric from reaching the sensor) is also determined.
  • Test results from ASTM F1959 must be reported for all garments that meet ASTM F1506 or ASTM F1891.Additionally, ASTM F1959 is used to determine a pass/fail criteria for ASTM F1891.

The standard can be purchased and downloaded from the ASTM website at http://www.astm.org/Standards/F1959.htm

ASTM F1891

Standard Specification for Arc and Flame Resistant Rainwear

This is the governing ASTM Standard for Flame Resistant Rainwear. The following are requirements of ASTM F1891:

  • A sample of fabric must self-extinguish with <2 second afterflame and <6″ char length according to ASTM Test Method D6413.
  • In contrast to ASTM F1506, ASTM F1891 requires that each different color of the same fabric be tested.
  • The fabric must be tested for Arc Thermal Performance according to ASTM Test Method F1959. The results of the Arc Thermal Performance testing must be reported to the end user as an Arc Rating on a garment label. Rainwear that meets ASTM F1891 complies with OSHA 1910.269.  ASTM F1891 is a pass/fail standard with requirements for reporting information not considered for the pass/fail criteria. All garments that meet the requirements of ASTM F1891 must state so on a garment label.
  • Material must withstand water pressure of 30 psig without leaking. The seams of the rainwear must not exhibit any evidence of leakage when exposed to water at 3 psig for (2) two minutes.
  • Material shall have a trapezoidal tear resistance of 6 lbs. in the warp direction and 6 lbs. in the fill direction.
  • Materials attached to the rainwear shall be permanent and electrically non-conductive, and shall not degrade the performance of the rainwear.
  • Rainwear material shall be flame resistant and shall not melt and drip when tested in accordance with ASTM D6413-08 and shall exhibit no more than a 2 second after flame time and less than a 6” char length.

The standard can be purchased and downloaded from the ASTM website at http://www.astm.org/Standards/F1891.htm

CSA Z462 (Canada)

CSA Z462 (Canada): Workplace Electrical Safety

CSA Z462 addresses workplace electrical safety and is considered best-practice in Canada. It is used by nearly all Canadian companies that deal with energized electrical equipment, with some exceptions. For example, CSA Z462 does not generally apply to watercraft, railways, and some aspects of communications and utilities work. The standard has recently been updated and harmonized with additional Canadian standards, including CSA Z460, Control of hazardous energy – Lockout and other methods; M421-16, Use of electricity in mines; and Parts I, II, and III of the Canadian Electrical Code.

In terms of protective clothing, CSA Z462 references two primary standards:

To be compliant to CSA Z462, garments must meet one of these two standards. All garments compliant to these standards are arc rated, and the arc rating is used to determine the PPE category of the garment.

CSA Z462 offers two basic methods for selecting PPE:

  1. The incident energy analysis method is straightforward, breaking up required PPE at 12 cal/cm² and requiring that the arc rating of the system meet or exceed the estimated incident energy.
  2. The arc flash PPE category method is more commonly used and specifies five PPE categories, as shown in the chart below:
    Arc Flash PPE Category
    In order from lowest to highest level of protection
    Minimum Arc Rating
    Measured in cal/cm2
    CAT 1 ≥ 4
    CAT 2 ≥ 8
    CAT 3 ≥ 25
    CAT 4 ≥ 40
    CAT 5 ≥ 75

  • The five categories are delineated according to the risk associated with specific tasks, based on factors including potential incident energy and working distance.
  • The categories range from 1 to 5, with 1 being the lowest amount of arc flash protection required, and category 5 (added in 2021) being the highest.
  • Each category has suggested garment systems, as well as a minimum arc rating for the garment system.

Additional guidance on underlayers and proper wear is offered by this standard:

  • Non-AR underlayers may be worn under AR PPE, as long as the PPE system’s arc rating is sufficient to prevent breakopen of the innermost AR layer at the expected incident energy level. This is to prevent ignition of non-AR underlayers.
  • Non-AR garments cannot to be used to increase the arc rating of the garment system.
  • Meltable fibres (such as polyester, polypropylene, etc.) shall not be used in underlayers, but undergarments and socks can contain incidental amounts of elastic. AR layers can contain some amount of meltable fibres, as long as the fabrics meet the requirements of ASTM F1506 or ASTM F1891.
  • PPE must be worn as intended – zippers fully zipped, cuffs buttoned, and shirts tucked in.
  • Tight-fitting clothing should be avoided. This is because a tighter fit reduces the protective air gap between PPE and the body, thereby increasing the potential for injury.
  • Garments must provide necessary protection and should not interfere with tasks.

The CSA Z462 standard was most recently updated in 2021. This edition included the addition of arc flash PPE category 5. This new category, with a minimum arc rating of 75+ cal/cm², requires the highest level of arc flash protection.

This CGSB Standard was withdrawn in December 2022. Please refer to NFPA 2112 [MU1.1]- Standard on Flame-Resistant Clothing for Protection of Industrial Personnel Against Short-Duration Thermal Exposures from Fire.

CSA Z462:21 can be purchased and downloaded from the CSA Group website using the link below: https://www.csagroup.org/store/product/CSA%20Z462%3A21/

Flash Fire Standards

NFPA 2112

Standard on Flame-Resistant Clothing for Protection of Industrial Personnel Against Short-Duration Thermal Exposures from Fire

NFPA 2112 specifies the minimum performance requirements and test methods for flame-resistant fabrics and components and the design and certification requirements for garments for use in areas at risk from flash fires. It establishes specific criteria for testing garments using the ASTM F1930 test method and the ASTM D6413 test method.

  • Using the ASTM F1930 manikin test, NFPA 2112 requires less than 50% 2nd and 3rd degree burn to pass. Garments are exposed to a 3-second engulfment fire at 2 cal/cm2and the total predicted body burn is measured. The test is three seconds – for two reasons:
    1. In theory, that is the upper limit of flash fire duration, and
    2. It is the area of greatest variability in results, affording the most accurate differentiation of fabric performance. The upper limit is 50% burn because survival rates plummet as TBSA (total body surface area) burns exceed that level.
      • Garments must be cut to a standard pattern, size 42-RG coverall, and tested over 100% cotton t-shirt and briefs.
      • Tyndale’s “Flash Fire Rated” clothing is defined as having 50% or less predicted body burn in 3 seconds, according to the specifications of NFPA 2112 (ASTM F1930 test method).
      • The fabric must not melt, drip, or have more than 2 seconds afterflame or 4.0 inches char length when tested and after 25 launderings when using ASTM D6413 test method.

Note: NFPA 2112 requires a maximum 4-inch char length when a garment is tested according to ASTM D6413. ASTM F1506, (Standard Performance Specification for Flame Resistant Textile Materials for Wearing Apparel for use by Electrical Workers Exposed to Momentary Arc and Related Thermal Hazards) requires a maximum 6-inch char length when ASTM D6413 is used. As long as the fabric sample does not ignite and continue to burn (called BEL for Burn Entire Length), char lengths at or below 6” are not meaningful predictors of thermal protective performance of the fabric in flash fire. In other words, some fabrics with relatively low char lengths have significantly higher body burn percentages in the manikin test than other fabrics with relatively higher char lengths. Char length differences below 6” do not correlate to protective performance or ASTM F1930 manikin test results, and we do not recommend inclusion of char length in specifications for this reason.

 

NFPA 2112 requires the following:

  • All garments must have a product label or labels permanently and conspicuously attached to each flame-resistant garment.
  • All garments labeled as compliant with NFPA 2112 must meet or exceed all applicable requirements specified in this standard and shall be UL certified
  • The UL certification organization’s label, symbol, or identifying mark shall be attached to the product label, be part of the product label, or be immediately adjacent to the product label.
  • NFPA 2112 outlines 17 test methods, including four pass/fail tests: flame resistance, manikin testing, thermal shrinkage resistance, and heat resistance. The other tests are report-only; that is, data is collected and reported, but it is not used to pass or fail a fabric.

The most recent update to NFPA 2112 is the 2023 edition. Changes to the standard made in 2018 that are related to flame resistant protective apparel include:

  1. Updated Title and New Terminology:
  • The term “flash fire” was changed to “short-duration thermal exposure from fire” throughout the standard, including the title. According to the standard, short-duration thermal exposure from fire is defined as “A period of egress from or accidental exposure to thermal events, including but not limited to, vapor cloud fires, jet flames, liquid fires (pool fires or running liquid fires), solids fires (fires of solid materials or dust fires), or warehouse fires. ”The term “inherent flame resistance” has been added to the standard from NFPA 1971, Standard on Protective Ensembles for Structural Fire Fighting and Proximity Fire Fighting. Inherent flame resistance is defined as “Flame resistance that is derived from the essential characteristic of the fiber or polymer,” according to the standard.
  1. Head, Neck, and Hand Protection Included: NFPA 2112-18 now applies to the design, manufacturing, and certification of shrouds/hoods/balaclavas, defined as items intended to protect the head and/or neck, and gloves, defined as garments designed to protect the hands and wrist.
  • Shroud, hood, and balaclava fabric shall not melt and drip, separate, or ignite during the heat resistance test and should also comply with the following requirements:
    • Spaced method Heat Transfer Performance (HTP) > 6.0 calories per centimeter, and Contact method HTP ≥ 3.0
    • Char length ≤ 4.0 inches (as received and after 100 industrial laundries)
    • After flame time ≤ 2.0 seconds (as received and after 100 industrial laundries)
    • Thermal shrinkage ≤ 10.0%
  • FR gloves shall meet all of the criteria above and may not exceed 5.0% of their original weight in consumed material.
  • It’s important to note that the ASTM F1930 Thermal Manikin Test is not required for fabrics for use in shrouds, hoods, balaclavas, and gloves.
  1. Cold Weather Insulation Guidance: The standard now provides guidance for FR cold weather insulation. The standard states that a flame resistance test is performed according to the ASTM D6413 Vertical Flame Test, and the NFPA 2112 performance criteria require the fabric to self-extinguish, not melt and drip, result in a char length of fewer than 4.0 inches, and have an after flame of fewer than 2.0 seconds once removed from the direct flame.
  1. Non-FR Emblems: Annex A.7.1.2.1 was added to specify requirements for non-flame resistant (non-FR) emblems. No more than five non-FR emblems may be attached to the exterior of a garment, Individual emblems may not cover an area exceeding 16 square inches and combined, the non-FR emblems are limited to covering an area of 40 square inches per garment. The NFPA 2112 standard is available at: https://www.nfpa.org/codes-and-standards/nfpa-2112-standard-development/2112

 
NFPA 2112 is available for complimentary viewing online or download or purchase at: https://www.nfpa.org/codes-and-standards/nfpa-2112-standard-development/2112

NFPA 2113

Standard on Selection, Care, Use, and Maintenance of Flame-Resistant Garments for Protection of Industrial Personnel Against Short-Duration Thermal Exposures from Fire

NFPA 2113 is a companion standard to NFPA 2112 and describes the selection, care, use, storage and maintenance of clothing used to protect against flash fire. It offers recommendations on best practices to follow and is a helpful guide for users and administrators of FR clothing programs. The standard was last updated in 2025.

  • Per NFPA 2113, the first step in the selection process is to conduct a thorough hazard assessment to establish the need for FR clothing.
  • Next, you should investigate the types of FR clothing designs available to determine which type will offer workers the best protection against the risks identified in your hazard analysis.
  • Finally, use the results of the two previous steps to develop specifications to guide the selection and purchase of appropriate FR clothing for your workforce.

Once FR clothing has been purchased and distributed to your employees, they need training in the proper use, care, and maintenance of the garments to ensure they provide full protection. This includes things like:

  • Wearing the garments properly to ensure full coverage,
  • How to launder the garments to preserve their FR properties
  • Instructions for repairing damaged garments
  • How to know when a garment can’t be repaired and needs to be retired from use.

Manufacturers and suppliers of FRC provide much of this information through garment labeling and additional materials. The NFPA 2013 standard provides further, specific guidance on what information and training you need to provide to your employees. But in the end, it is your responsibility to train your workers and to monitor their compliance with proper use and maintenance requirements.

The standard is available for complimentary viewing online or to purchase a downloadable copy:  https://www.nfpa.org/codes-and-standards/nfpa-2113-standard-development/2113

ASTM F1930

ASTM F1930: Standard Test Method for Evaluation of Flame-Resistant Clothing for Protection Against Fire Simulations Using an Instrumented Manikin

ASTM F1930 specifies a standard process for measuring the average predicted body burn of a fabric based on a laboratory flash fire simulation. It tells us how to perform a manikin test, but not what to test for. NFPA 2112 sets the pass/fail criteria at <50% 2nd and 3rd degree burn in a 3 second exposure.

  • The fabric is sewn into a standard coverall pattern. This coverall is size 42R, with no pocket bags, cuffs pockets or other discretionary areas of multiple layer fabric.
  • The coverall is placed on an instrumented manikin, which has at least 100 thermocouples on its surface, excluding the hands and feet.
  • Sensors measure the performance of single layer garments or protective clothing ensembles in a simulated flash fire environment with controlled heat flux, flame distribution, and duration.
  • Heat transmitted to each sensor on the surface of the manikin records the location, extent and severity of burn injury. Total 2nd and 3rd degree burn is the focus.
  • The visual and physical changes to the single layer garment or protective clothing ensemble are recorded to aid in understanding how the burn injury results can be interpreted.
  • Afterflame is recorded for duration, but not for extent of body surface.
  • The measurements obtained and observations noted can only apply to the particular garment(s) or ensemble(s) tested using the specified heat flux, duration, and flame distribution.

This standard should be used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions and should not be used to describe or appraise the fire-hazard or fire-risk of materials, products, or assemblies under actual fire conditions.

However, results of this test may be used as elements of a fire-hazard assessment or a fire-risk assessment which takes into account all of the factors which are pertinent to an assessment of the fire hazard or fire risk of a particular end use.

The 2023 edition of ASTM F1930 updated the previous 2018 version and continues to refine terminology, references, and procedural language for consistency with current ASTM practices. The standard also incorporates updated references, clarifies limitations of the test method, and emphasizes that the procedure is intended for comparative performance evaluation rather than quality assurance or direct prediction of real-world injury outcomes.

The standard can be purchased and downloaded from the ASTM website at https://store.astm.org/f1930-23.html

ASTM F2733

ASTM F 2733: Standard Specification for Flame-Resistant Rainwear for Protection Against Flame Hazards

This specification establishes applicable test methods, minimum physical and thermal performance criteria, a suggested sizing guide, and suggested purchasing information for rainwear for use by workers who are potentially exposed to industrial hydrocarbon fires or other petrochemical fire hazards. Performance requirements of ASTM F2733 are as follows:

  • Flame Resistance: Rainwear material shall be flame resistant and shall not melt and drip when tested in accordance with ASTM D6413/D6413M and shall exhibit no more than a 2-second afterflame time and less than a 4” char length.
  • Thermal Protection: Rainwear material shall be tested in accordance with ASTM F1930, a design test, after 1 washing and 1 drying. Testing parameters are set at heat flux of 84 2.0 +/- 0.05 cal/cm2and an exposure time of 3 +/- 0.1 seconds.
  • Flash Fire Protection: Total body burn must be not more than 40%.
  • Leak Resistance: Material must withstand water pressure of 30 psig without leaking. The seams of the rainwear must not exhibit any evidence of leakage when exposed to water at 3 psig for (2) two minutes.
  • Tear Resistance: Material shall have a trapezoidal tear resistance of 6 lbs. in the warp direction and 6 lbs. in the fill direction.
  • Moisture Vapor Transmission (Breathability): If the rainwear is advertised as being breathable, it must be tested.
  • Markings and Reflective Materials: These materials attached to the rainwear shall be permanent and shall not degrade the performance of the rainwear.

The ASTM F2733 Standard was most recently updated in 2021. Changes in this latest edition include terminology updates, harmonization with related ASTM flame-resistant clothing standards, clarification of testing and labeling requirements, updates to referenced standards, and editorial revisions for consistency with current ASTM formatting.

 

The standard can be purchased and downloaded from the ASTM website at https://store.astm.org/f2733-21.html

Protective Footwear Standards

ASTM F2412

ASTM F2412: Standard Test Methods for Foot Protection

The ASTM F2412 test methods measure resistance of footwear to hazards that may result in injury to the worker.

These methods may be used to test for compliance to minimum performance requirements in established safety standards. The test methods can be used to determine the effectiveness of the footwear to provide any one, or all of the following protections:

  • Impact resistance to eliminate or diminish the severity of injury caused by objects striking the foot, and in particular in the toes and metatarsal region
  • Reduced buildup of static electricity from the wearer to the ground
  • Shock absorbance
  • Puncture resistance and chain saw resistance
  • Dialectic insulation to reduce the possibility of injury when exposed to a high voltage charge.

The standard describes the specific methods, including diagrams of the equipment used (when appropriate), to conduct the testing for each of the protections listed above.

The standard can be viewed and purchased from the ASTM website at: http://www.astm.org/Standards/F2412.htm

ASTM F2413

ASTM F2413: Standard Specification for Performance Requirements for Protective (Safety) Toe Cap Footwear

ASTM F2413 covers the minimum design, performance, testing, labeling, and classification requirements for footwear designed to protect against a variety of workplace hazards that can potentially result in injury. Replacing the specification ANSI Z41, ASTM F2413 should be referenced when purchasing protective footwear to ensure minimum performance requirements are met. OSHA incorporates this reference standard in 29 CFR Part 1910.136 – Foot protection.

Footwear is third-party tested as per ASTM F2412: Standard Test Methods for Foot Protection to measure resistance to hazards that may result in worker injury. Each protection criteria test is administered three times, and the lowest score is used to ensure compliance with minimum performance requirements.

Footwear certified as meeting the ASTM F2413 standard must primarily meet the protection requirements for (I) impact resistance and (C) compression resistance. Then, additional protection criteria, if met, are labeled accordingly, depending on specific footwear protection requirements. Footwear labels should clearly state which of the requirements the footwear meets. Requirements are as follows:

  • Impact resistance for the toe area of footwear. While a steel toe is not required, a protective toe cap should be a permanent part of the footwear. Previous versions of ASTM F2413 specified several levels of impact protection; the most recent update to the standard requires the highest level, protecting against impacts up to a 75-pound force.
  • Compression resistance for the toe area of footwear. Earlier versions of ASTM F2413 specified several levels of compression protection, but the latest update requires the highest level, protecting against compression from a rolling object weighing up to 2,500 pounds.
  • Metatarsal protection reduces the chance of injury to the metatarsal bones at the top of the foot. Footwear should be designed, constructed, and manufactured so that a metatarsal impact guard is positioned partially over the protective toe cap and extended to cover the metatarsal bone area. Earlier versions of ASTM F2413 specified several levels of metatarsal protection, but the latest update requires the highest level, protecting against impacts up to a 75-pound force.
  • Electric hazard (EH) resistant footwear has an outsole and heel that protects workers from electric shock hazards. While OSHA requires employers to first and foremost take protective measures to prevent electrical hazards from occurring, electric hazard (EH) safety shoes provide a supplemental form of protection for at-risk workers. The electrical hazard protection of EH footwear is severely diminished in wet conditions or where footwear can be contaminated with conductive materials, such as metal shavings. In these environments, dielectric overshoes should be worn.
  • Static dissipative (SD) footwear is worn in computer component handling facilities and environments where static electricity generated by manufacturing processes can cause problems. This type of footwear reduces excess static electricity by conducting a charge from body to ground while simultaneously maintaining a high level of resistance to protect the wearer. There are now three levels of SD protection listed on labels: SD10, SD35, or SD100.
  • Conductive (Cd) footwear  dissipates static electricity much faster than SD-rated footwear and is worn in highly flammable or explosive environments, dissipating static electricity from the body, through the shoes, and into the ground. This reduces the possibility of explosives or volatile chemicals igniting from a static spark. Static dissipative and conductive footwear both conduct electricity and therefore should not be worn where electrical hazards could be present.
  • Puncture resistance of footwear bottoms.  A puncture-resistant plate should be positioned between the insole and outsole and made an integral and permanent part of the footwear.

Labeling and Identification:

The ASTM F2413 label uses a specific three or four-line format to identify the type of footwear and the hazards it protects against:

  • Line 1: Identifies compliance with ASTM F2413 and indicates the standard’s year of issuance.
  • Line 2: Identifies gender of the wearer (M/F) and meets the protection requirements for impact resistance and compression resistance.
  • Lines 3 and 4: Identifies additional protection criteria for specific types of hazards. Metatarsal (Mt) resistance is now indicated on line 3.

TABLE 1 Examples of Marking and Identification  
Identification Description
Example A
Line 1 ASTM F2413–18 Standard-year of issue (2018) Complies with the performance requirement of F2413 issued in 2018. Footwear worn by female worker has impact resistance and compression resistance. Also meets the standard for metatarsal impact resistance. The footwear is electrical hazard resistant.
Line 2 F/I/C Female/Impact/Compression
Line 3 Mt   EH Metatarsal   Electrical Hazard
Example B
Line 1 ASTM F2413–18 Standard-year of issue (2018) Complies with the performance requirement of F2413 issued in 2018. Footwear worn by male worker has impact resistance and compression resistance. Also meets the standard for puncture-resistant footwear.
Line 2 M/I/C Male/Impact/Compression
Line 3 PR Puncture Resistant
Example C
Line 1 ASTM F2413–18 Standard-year of issue (2018) Complies with the performance requirement of F2413 issued in 2018. Footwear worn by male worker has impact resistance and compression resistance. Footwear also meets the highest class rating (100, vs. 35 or 10) for static dissipation and meets the standard for conductive protection.
Line 2 M/I/C Male/Impact/Compression
Line 3 SD 100 Static Dissipative
Line 4 Cd Conductive

 

From ASTM F2413-18 – Section 6, Labeling and Identification.

The label must list the requirements the footwear meets, as demonstrated by the examples above. Footwear may protect against seven categories. The protection provided is described on the label using the abbreviation shown below.

  • I – Impact-resistant footwear (Section 5.2)
  • C – Compression-resistant footwear (Section 5.3)
  • Mt – Identifies footwear designed to be impact resistant to the top of the foot (metatarsal) (Section 5.4)
  • Cd – Identifies protection against conductive hazards (Section 5.5)
  • EH – Identifies footwear with outsole and heel made of electrical insulation properties; one that is also shock resistant (Section 5.6)
  • SD – Identifies footwear designed to reduce the accumulation of excess static electricity (Section 5.7)
  • PR – Identifies footwear designed to be puncture-resistant (Section 5.8)

The numbered section at the end of each description provides a reference to the section in ASTM 2413-18 that describes the performance requirements a product must meet before it can be labeled as protecting against the specific hazard. It also describes the testing procedure used.

The standard can be purchased and downloaded from the ASTM website at http://www.astm.org/Standards/F2413.htm.

ASTM F2892

ASTM F2892: Standard Specification for Performance Requirements for Soft Toe Protective Footwear (Non-Safety / Non-Protective Toe)

ASTM F2892 is the Standard Specification for Performance Requirements for Soft Toe Protective Footwear (Non-Safety / Non-Protective Toe). According to ASTM F2892, “This specification covers minimum requirements for the performance of footwear to provide protection against a variety of workplace hazards other than the toe area that can potentially result in injury.”

While ASTM standards F2412 and F2413 provide test methods and performance requirements for footwear requiring a safety toe cap, many jobs in the industry do not require impact or compression toe protection. The ASTM committee developed non-safety toe cap (soft toe) requirements allowing manufacturers to demonstrate the performance level of soft toe footwear.

The primary purpose of ASTM F2892 is the certification of soft toe protective footwear. In order for footwear to bear the ASTM marking, certification must be performed by independent third party laboratories.

The specification contains performance requirements to protect workers’ feet against electrical charge-based and puncture hazards:

  • Conductive properties (Cd), which reduce hazards that may result from static electricity buildup; and reduce the possibility of ignition of explosives and volatile chemicals.
  • Electric hazard protection (EH), to protect wearers when accidental contact is made by stepping on a live electric wire.
  • Static dissipative properties (SD) to reduce hazards due to excessively low footwear electrical resistance that may result where SD footwear is required.
  • Puncture resistance (PR) footwear devices.

Note: Description of protective properties is paraphrased from ASTM F2892. This standard also provides examples of labeling for soft toe safety or occupational footwear. Proper labeling and identification ensures the wearer that the footwear meets the required minimum performance as stated in this specification F2892.

The standard can be purchased and downloaded from the ASTM website at https://store.astm.org/f2892-24.html

High-Visibility Standards

ANSI/ISEA 107

ANSI/ISEA 107: American National Standard for High-Visibility Safety Apparel

Last updated in 2020, the American National Standards Institute (ANSI) for High Visibility Safety apparel standard provides consistent, authoritative guidelines for the selection and use of high-visibility apparel in the United States. The standard is intended as a guide to aid manufacturers, consumers and the general public in the use of high visibility safety apparel.

ANSI/ISEA 107 offers performance specifications and outlines minimum amounts of background material and retro reflective material (high visibility tape), tape placement on garment, test methods, garment labeling, and luminance factor, among other factors.

The 2015 update consolidates the requirements of ANSI/ISEA 107 and ANSI/ISEA 207 (American National Standard for Public Safety Vests) to establish a single, comprehensive document that considers all occupational tasks. While the standard continues to present three performance classes of garments (see below) based on the amount of visible materials and design attributes incorporated into the final configuration, it also identifies garment types based on expected use settings and work activities being performed. These are designated as off-road (type O), roadway and temporary traffic control (type R), or public safety activities (type P).

In response to concerns expressed by smaller-sized wearers about the risk of having to wear oversized garments that present a catch hazard, the committee included provisions for Type R Performance Class 2 and Performance Class 3 garments in the smallest size offered to utilize a reduced amount of background material to allow for sizing more appropriate for smaller workers. It is stressed that these reduced amounts are intended to address the smaller sized workers’ needs specifically, that only the smallest size offered for any one garment be allowed to deviate from the stated minimum and that the resulting configuration using these amounts be consistent with the other sizes for that particular garment.

Manufacturers may now also opt to have high-visibility garments labeled as flame resistant. To be marked as flame resistance, high-visibility garments must fully comply with the requirements of one of the following methods:

  • ASTM F1506-10a, Standard Performance Specification for Flame Resistant and Arc Rated Textile Materials for Wearing Apparel for use by Electrical Workers exposed to Momentary Electric Arc and Related Thermal Hazards
  • ASTM F1891-12, Standard Specification for Arc and Flame Resistant Rainwear
  • ASTM F2302-08, Standard Performance Specification for Labeling Protective Clothing as Heat and Flame Resistant
  • ASTM F 2733-09, Standard Specification for Flame Resistant Rainwear for Protection Against Flame Hazards
  • NFPA 1977, Standard on Protective Clothing and Equipment for Wildland Firefighting, 2011
  • NFPA 2112, Standard on Flame-Resistant Garments for Protection of Industrial Personnel Against Flash Fire, 2012

Finally, in recognition of the growing use of high-visibility accessory items such as arm bands or headwear, the standard now defines minimum material requirements for these accessories. New labeling requirements will identify the garment by performance class, type and by its flame resistance characteristics as defined in the standard. ANSI/ISEA 107 also expands the examples of garment configurations to illustrate compliant and non-compliant designs.

 

 Class I

These garments are intended for workers who have ample separation from vehicular traffic that does not exceed 25 mph.

  • Class I garments are often safety vests; they are recommended for parking service attendants, workers in warehouses with equipment traffic, shopping cart retrievers, sidewalk maintenance workers, and delivery vehicle drivers.

 

Class II

Class II garments are for users who need greater visibility in poor weather conditions and whose activities occur near roadways where traffic speeds exceed 25 mph.

  • This class of garment is suitable for railway workers, school crossing guards, parking and toll gate personnel, airport ground crews, and law enforcement personnel directing traffic.

 

Class III

Class III garments provide the highest level of visibility to workers in high-risk environments that involve high task loads, a wide range of weather conditions and traffic exceeding 50 mph. Class III garments provide coverage to the arms and/or legs as well as the torso, and can include pants, jackets, coveralls, or rain wear.

  • The standard recommends all roadway construction personnel and vehicle operators, utility workers, survey crews, emergency responders, railway workers, and accident site investigators wear these garments.

A Final Rule enacted by the Department of Transportation – Federal Highway Administration took effect on November 24, 2008. Final Rule 23 CFR Part 634 requires that workers on a Federal-aid highway exposed to vehicular traffic or construction equipment within the work area wear high-visibility safety apparel.  This rule specifies classes of workers commonly impacted. They include:

  • Highway construction and maintenance crews
  • Survey crews
  • Utility workers
  • Road crews and volunteer clean-up groups
  • Responders to incidents  and law enforcement personnel

The ANSI 107-2020 standard is available to purchase online: https://webstore.ansi.org/Search/Find?in=1&st=ANSI+107

CSA Z96 (Canada)

CSA Z96 (Canada): High-visibility safety apparel

CSA Z96, the Canadian Standards Association standard for high-visibility safety apparel (HVSA), is typically considered best practice in Canada and is a requirement for some provinces, including Manitoba and British Columbia. It provides specifications for occupational clothing worn to visually signal the presence of workers by making them clearly noticeable in hazardous situations under any light conditions, including illuminations by vehicle headlights.

CSA Z96 specifies performance requirements for HVSA, including:

  • Background material
  • Retroreflective material (high visibility tape)
  • Minimum coverage for background and retroreflective materials
  • Tape placement on garments that minimally includes two vertical stripes on the front, a horizontal stripe encircling the waist, and an X pattern on the back.

The standard has three classes of garments based on the coverage of retroreflective and background fabric incorporated in the garment. It also includes three levels, which are based on the width and performance of the retroreflective trim used in the garment.

Garment class is based on the amount of fluorescent or bright background material present in a garment. Body coverage ranges from Class 1, which requires only a harness configuration, to Class 2, which requires torso coverage, to Class 3, requiring torso coverage with additional arm and leg band retroreflective striping. Examples of HVSA for each garment class are shown below:

Class 1 garment

Class 1 garments give good visibility with the lowest required body coverage and require a basic harness, with either triple tape (e.g., yellow/silver/yellow or orange/silver/orange) or combined-performance striping, which is retroreflective material that is also fluorescent. The reflective portions can be Level 1, Level 2, or Level FR.

Class 2 garment

Class 2 garments provide superior visibility with moderate body coverage, requiring bright or fluorescent background material covering the torso and Level 1 or 2 striping in a harness pattern. Striping can be silver, combined performance, or even triple-tape, as long as the retroreflective portion is 50mm (2″) wide. Class 2 has a special exception for bib overalls, which can be compliant even if the striping does not extend over the shoulders, but additional leg band striping is required.

Class 3 garment

Class 3 garments provide the best visibility and are worn in high-risk situations, such as low-light or nighttime conditions or when visibility is required from long distances due to vehicle speeds exceeding 80 km/h (50 mph). Class 3 requires bright or fluorescent background material on the same areas as Class 2, with the addition of arm and leg bands.

Garment levels are determined by the width and performance of the retroreflective trim used. Level FR is the lowest level of allowable retro reflectivity and the only level at which the width of the retroreflective trim can be 19 mm (or roughly ¾”). Level FR garments must also be flame resistant. For Levels 1 and 2, the retroreflective trim must be at least 50 mm (or 2”) wide and contrast with the background material. Level 2 offers the highest retroreflective performance and is typically used in the lowest light conditions.

The CSA Z96 standard does not have specific requirements stating which Classes and Levels to use for different conditions but does offer guidance on how to make these decisions. It suggests that decisions should be based on:

  • Vehicle speed, volume, and control
  • Considerations for contrasting with surrounding elements
  • Light conditions
  • Other notable hazards such as the risk of flame exposure or electric arc

The fourth edition of CSA Z96 was published in 2022. Significant changes to this edition include:

  • Updated abbreviations and definitions to align with terminology found in ANSI/ISEA 107.
  • Changes to reference publications to remove the withdrawn CGSB 86.1 and add ASTM and ISO references.
  • A Class 2 requirement for leg striping on bib-style overalls was added to Clause 4.5.
  • Additional Clause content updates.
  • Annex materials were revised.

CSA Z96 can be purchased and downloaded from the CSA Group website using the link below:
https://www.csagroup.org/store/product/CSA%20Z96%3A22/

General Protective Clothing Standards

OSHA General Duty Clause

The OSHA General Duty Clause requires that employers provide employees a workplace that are free from known hazards. Employers must follow OSHA guidelines by law. Employees are required to act in compliance with OSHA guidelines by law.

This clause is intended to be all-encompassing, ensuring that employees have a safe work environment. The General Duty Clause has been cited in situations where federal law does not exist and workers have been exposed to hazardous conditions. For example, OSHA has enforced NFPA 70E by citing the General Duty Clause.

For more information, the general duty clause is available on OSHA’s website:
http://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=OSHACT&p_id=2743

OSHA 1910.132

OSHA 1910.132: General Requirements under Subpart I, Personal Protective Equipment

OSHA 1910.132 offers employers guidelines on protective equipment for workers.

“Personal equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, shall be provided, used and maintained in a sanitary and reliable condition wherever it is necessary by reason of hazards of processes or environment, chemical hazards, radiological hazards, or mechanical irritants encounter in a manner capable of causing injury or impairment in the function of any part of the body through absorption, inhalation or physical contact. ”

The standard delivers guidelines for employers on what is required including hazard assessment, employee training in proper care and use of personal protective equipment (PPE), and identifies the party responsible for paying for the required PPE.

For more information, view the details at:

http://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=STANDARDS&p_id=9777

In March 2010, OSHA issued an addendum regarding specific industries susceptible to the flash fire hazard—namely drilling, servicing, and production-related occupations—and mandating the use of flame resistant (FR) clothing in these occupations under certain working conditions.

OSHA explains, “The use of FR greatly improves the chance of a worker surviving and regaining quality of life after a flash fire. FR can significantly reduce both the extent and severity of burn injuries to the body.”

Citing accident and injury data for flash fire incidents, which have resulted in a 16% fatality rate in oilfields in recent years, OSHA reinforces the value of FR clothing in the event of engineering and administrative control failure.

The addendum is available by clicking on the following link: http://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=INTERPRETATIONS&p_id=27296

ANSI Z87.1

ANSI Z87.1: American National Standard for Occupational and Educational Personal Eye and Face Protection Devices

The ANSI/ISEA Z87.1 standard sets forth requirements for the design, construction, testing, and use of eye protection devices, including standards for impact and penetration resistance. All safety glasses, goggles, and face shields used by employees under OSHA jurisdiction must meet the ANSI/ISEA Z87.1 standard. The eyewear standard includes the following minimum requirements:

  • Provide adequate protection against the hazards for which they are designed
  • Provide reasonable comfort
  • Fit securely, without interfering with movement or vision
  • Be capable of being disinfected, if necessary, and be easy to clean
  • Be durable
  • Fit over, or incorporate, prescription eyewear

From a practical perspective, eye and face protective devices are important to electric workers exposed to arc flash, where the arc blast poses a hazard or for workers exposed to flash fire, where there is the potential for a secondary blast. The equipment cited protects workers from projectiles encountered.

You can download the ANSI/ISEA Z87.1 Standard here.

ASTM D6413

Standard Test Method for Flame Resistance of Textiles (Vertical Test)

ASTM D6413/D6413M is the defining test method for compliance with OSHA 1910.269 and one of the most commonly used tests on flame resistant fabrics. Adopted from Federal Test Standard No. 191A, method 5903.1, the vertical flame test has been used for many years.

  • The purpose of this test is to determine whether a fabric will continue to burn after the source of ignition is removed.
  • A 12” specimen of fabric is suspended in an enclosed chamber (secured on three sides).  The cut edge of the fabric on the bottom is exposed to a controlled methane flame for 12 seconds.
  • After exposure to the flame, afterflame, afterglow, and char length are measured.  Five tests are performed and the results are averaged and reported as the test result.
  • ASTM D6413/D6413M is used to determine a pass/fail criteria for ASTM F1506, which requires a maximum char length of 6 inches.
  • Note: ASTM F1506 requires a maximum char length of 6 inches under this test method, whereas NFPA 2112 requires a maximum of 4 inches.  A 6-inch char length is more universally accepted as the maximum.  Char length of FR fabrics does NOT correlate to thermal protective performance in the manikin test. As long as the fabric sample does not ignite and continue to burn (called BEL for Burn Entire Length) char lengths at or below 6” are not meaningful predictorsof thermal protective performance of the fabric in flash fire. In other words, some fabrics with relatively low char lengths have significantly higher body burn percentages in the manikin test than other fabrics with relatively higher char lengths. We do not recommend inclusion of char length in specifications for this reason.

The standard can be purchased and downloaded from the ASTM website at https://store.astm.org/d6413_d6413m-22.html

ASTM F1449

Standard Guide for Industrial Laundering Care and Maintenance of Flame Resistant or Arc Rated Clothing

There is no Federal or State law or standard that says that FR clothing should or must be laundered industrially. In fact, in recent years, more and more employees have opted to launder their FR clothing at home for the sake of convenience. However, industrial laundering is still offered in many workplaces. ASTM F1449 outlines the industrial laundering process. This guide outlines the responsibilities of the fiber, fabric, and clothing manufacturers, as well as the processor, the processor’s chemical supplier, and the end user.

Responsibilities of the manufacturer include:

  • Flame, thermal, and arc resistant clothing must be specified by fiber, fabric, and finish.
  • Category A clothing is made exclusively from fabric made of inherently flame-resistant (FR) fibers that are tolerant to high-laundry and finishing temperatures
  • Category B is inherently FR fabrics that have limitations on the maximum temperature for laundering and finishing
  • Category C is FR Treated fabrics
  • Category D is FR fabrics that are a combination of fabrics that are Type A, and/or B, and/or C.
  • Category X includes FR clothing with specific label instructions prohibiting laundering (i.e. “Dry Clean Only” or “Do Not Wash”). Information must be provided on the performance characteristics and maintenance needs

Responsibilities of end users include:

  • Care instructions must be followed on label
  • To appropriately determine when a garment has reached the end of its useful life and should be retired from service

The standard also provides a brief overview on “laundering wash formulas,” which should take into consideration the following:

  • Water temperature
  • Drying temperature
  • Water hardness
  • Mechanical action
  • Machine load factor
  • Soil sorting
  • Wash room chemistry
  • Finishing temperature
  • Alkalinity of detergents
  • Use of bleach
  • Souring
  • Extraction
  • Cycle Times

The law does not require industrial laundering and industrial laundering is not necessary to maintain the protective qualities of FR clothing. The standard can be purchased and downloaded from the ASTM website at: https://store.astm.org/f1449-20r26.html

ASTM 2757

Standard Guide for Home Laundering Care and Maintenance of Flame Resistant or Arc Rated Clothing

ASTM F2757 is intended for use by flame resistant (FR) clothing program managers (such as safety personnel or program administrators) who have chosen to implement a home-laundered flame, thermal or arc resistant clothing program. Home laundering is a safe, cost-effective alternative to industrial laundering and can help preserve the useful life and protective qualities of FR clothing.

This guide describes the key components involved in the home care and maintenance of flame, thermal, and arc resistant clothing. The following procedures are highlighted:

  • Garment manufacturers are responsible for providing information on their garments. The end user is also responsible for understanding the hazards present in the workplace and selecting appropriate personal protective equipment (PPE).
  • Recommendations are included for providing optimal care and preserving flame, thermal, and arc resistant properties, as well as increasing the wear life, appearance, and comfort of the clothing.
  • Laundry wash formulas should be developed by the processor and wash chemical supplier in collaboration with the clothing and fabric manufacturers based on several characteristics.
  • Removal from service is recommended under certain conditions. Garments that have un-repairable damage, are worn out, or are unusable for other safety reasons, are not to be reused and should be discarded.

Repairs of flame, thermal, and arc resistant clothing should be made from components equivalent to those used in the original manufacturing to avoid reducing the performance properties of the flame resistant garment.

Home laundering has become a widely accepted method to clean FR clothing in a variety of industries. The ASTM F2757 standard can be purchased and downloaded from the ASTM website at https://store.astm.org/f2757-20r26.html

ASTM F2302

Standard Performance Specification for Labeling Protective Clothing Which Provides Resistance to Incidental Exposures to Heat or Open Flame

ASTM F2302 establishes minimum requirements for labeling protective clothing that provides resistance to heat, flame, and melting for applications where the potential exists for incidental exposure to open flame, radiant heat sources, or hot surfaces which could melt or ignite materials.

The standard can be purchased and downloaded from https://store.astm.org/f2302-22.html.

✕