Do I Need Arc-Rated PPE to Open an Energized Breaker Panel?
March 6, 2025
Working on or around electrical hazards almost always requires personal protective equipment (PPE) – even in situations you might not expect. As part of our Do I Need AR PPE for That? series, we explore this common scenario in electrical work and whether arc-rated clothing is needed for safety and compliance.
The Direct Answer: Yes, in Most Practical Scenarios.
While many consider opening a breaker panel “low risk,” it is a very common moment for arc flash to occur. According to OSHA’s latest Arc Flash Guidance (released late 2024) and NFPA 70E, PPE is required while interacting with energized equipment, unless “normal operating conditions” are met. Read on to learn how NFPA 70E defines normal operating conditions.
Watch: Scott Margolin (VP of Technical) explains why opening a breaker panel isn’t as low risk as it may seem.
The 2024 OSHA Guidance: Why it Matters Now
In November 2024, OSHA released its first significant update to arc flash safety guidance in nearly 20 years. This guidance was issued specifically to address common causes of arc flash injuries and fatalities.
The 2024 guidance clarifies that:
- Low Voltage is Not Low Risk: Systems at 120/208V and 120/240V can sustain an arc flash long enough to ignite non-FR clothing and cause fatal burns.
- "De-energized" is Not the Same as LOTO: Equipment is not truly safe until a formal lockout/tagout (LOTO) and verification of absence of voltage have occurred. Simply turning a breaker to “off” is still considered energized work and requires arc-rated clothing.
What Is a “Normal Operating Condition”? [NFPA 70E 110.2 (B)]
To determine if you need PPE, you must assess if the equipment is in a “normal operating condition.” Per NFPA 70E section 110.2B, if any of these conditions are NOT met, arc flash risk is present and proper PPE, including arc-rated clothing, must be worn:
- The equipment is properly installed and maintained.
- All doors are closed and secured.
- All equipment covers are in place and bolted.
- There is no evidence of impending failure (e.g., arcing, buzzing, heat, or loose parts).
- The equipment is used within its manufacturer’s rating.
The Reality Check: In the field, can you prove the panel was properly maintained per NFPA 70E standards? Because these factors are often unknown, treating the panel as a potential hazard is the only way to ensure 100% compliance.
Debunking 4 Dangerous Breaker Panel Myths
Myth 1: “It’s only 120V, it can’t arc.”
The Truth: While high voltage jumps further, low voltage often has a higher fault current and longer clearing times. This means a low-voltage arc can actually release more heat energy than a high-voltage one.
Myth 2: “I’m just looking at the breakers.”
The Truth: The act of opening a hinged cover changes the air pressure and can disturb dust or loose components. If a fault is imminent, this physical interaction can trigger an arc.
Myth 3: “I turned the main breaker off, so I'm safe.”
The Truth: Unless you have performed LOTO and established an electrically safe working condition (ESWC), the line side (power side) of that breaker is still energized. If you drop a tool or a component fails, the arc will occur before the breaker can trip.
Myth 4: “Standard cotton is fine for this.”
The Truth: Non-FR cotton is as good as “fuel.” If an arc occurs, standard cotton clothing will ignite and continue to burn long after the arc has extinguished. AR/FR clothing is designed to self-extinguish, turning a potential fatality into a survivable “non-event.”
What Kind of PPE Do I Need?
At Tyndale, we believe offering electrical workers choice and ownership over their arc-rated and flame resistant clothing is the best approach to protection—but it is the employer’s responsibility to assess risks and determine the appropriate PPE for their employees to protect against the hazards they may face. According to OSHA 3151-12R 2003, employers must select PPE that provides a level of protection greater than the minimum required to protect employees from hazards.
Providing a baseline of arc-flash protection (such as an 8-cal or 12-cal uniform, depending on the hazard, helps ensure that workers are protected. This also eliminates decision fatigue and ensures that if a routine panel opening turns into a fault, the worker is wearing life-saving insulation that will not ignite.
Episodes:

Do I Need Arc-Rated PPE to Open a Residential Breaker Panel?
OSHA released new Arc Flash Guidance in November 2024 to ensure that arc-rated (AR) clothing and equipment is provided to...

Do I Need AR PPE to Use a Voltmeter or Multimeter?
In the past, many inside electricians didn’t wear arc-rated (AR) clothing or personal protective equipment (PPE) because they believed they...

The Truth About Lockout/Tagout and Arc-Flash PPE
We’re continuing our series on OSHA’s new arc-flash guidance by tackling a common question: Do you need arc-rated(AR) personal protective...

Do I Need AR PPE to Throw a Breaker?
As the industry absorbs OSHA’s new arc flash safety guidance and makes changes to comply and better protect workers, one...

Do I Need AR PPE for Low Voltage Work?
When you hear “low voltage,” it’s easy to assume low risk — but that assumption can be dangerous, even fatal....